Product characteristics The energy detector has three channels for connecting loads to up to three separate phases with a common neutral conductor. Each channel can measure:
- Voltage (eff.)
- Current (eff.)
- Active power
- Reactive power
Additionally, the active power and reactive power of all channels will be summed up and displayed as three-phase power values along with the mains frequency.
According to the parameterisation the measured values will be transmitted on the KNX bus, either cyclically and / or when the value changes. An additional telegram will be transmitted if certain values exceed or fall below a specified limit.
The following meters exist for each channel and for the three-phase values:
- 1 x energy meter total
- 1 x energy meter ¼ h value
- 3 x energy meter n
- 3 x energy intermediate meter n
New in version 01
- Direct measurement (without transformer)
- Transformer measurement (with external 75 A transformer, ratio 75:5, e.g. Phoenix Contact order key 2277611)
Technical data
Power supply via E1/N |
Rated voltage: |
AC 110 ... 240 V ~ |
Mains frequency: |
50/60 Hz |
Power consumption: |
max. 2 W |
Inputs E1 ... E3 |
Rated voltage range: |
AC 110 ... 240 V ~ |
Rated current range: |
4 mA ... 16 A |
Rated frequency: |
50/60 Hz |
Measurands: |
voltage (rms value) current (rms value) frequency active power (signed +/-) reactive power (signed +/-) active energy (signed +/-) |
External transformer |
Transformation ratio: |
75:5 |
Secondary current: |
0 ... 5 A |
Accuracy |
Direct measurement (without transformer): |
1 % of 200 mA ... 16 A |
Transformer measurement (75 A transformer, class 1): |
2 % of 7.5 A ... 75 A |
Pulses LED |
Direct measurement (without transformer): |
6400 / kWh |
Transformer measurement (75 A transformer): |
427 / kWh |
Pulse duration: |
4.9 ms |
Power loss |
Voltage measurement: |
≤ 0.03 W / phase |
Current measurement: |
≤ 0.8 W / phase |
Power consumption from mains: |
< 1 W |
Connection |
Connection mode: |
screw terminals |
single wire: |
1 x 0.5 ... 2.5 mm² |
stranded without ferrule: |
1 x 0.5 ... 2.5 mm² |
stranded with ferrule: |
1 x 0.5 ... 2.5 mm² |
Ambient temperature: |
−5 ... +45 °C |
Storage/transport temperature: |
−25 ... +70 °C |
Mounting width: |
72 mm (4 rail units) |
KNX medium: |
TP 256 |
Rated voltage KNX: |
DC 21 ... 32 V SELV |
Current consumption KNX: |
typical 10 mA |
Connection, KNX: |
terminal |
|