KNX medium: |
TP 256 |
Rated voltage KNX: |
DC 21 ... 32 V SELV |
Current consumption KNX: |
max. 6 mA |
Power loss: |
max. 4 W |
Ambient temperature: |
−5 ... +45 °C |
Storage/transport temperature: |
−25 ... +70 °C |
Control outputs |
Control voltage: |
1 ... 10 V |
Control current per output: |
max. 100 mA |
Cable length: |
max. 500 m (0.5 mm²) |
Switching outputs |
Contact type: |
floating relay contacts (μ contact) |
Switching voltage AC: |
AC 250 / 400 V |
Switching current 230 V AC1: |
16 A |
Switching current 230 V AC3: |
10 A |
Switching current 400 V AC1: |
10 A |
Switching current 400 V AC3: |
6 A |
Fluorescent lamps: |
16 AX |
Switching voltage DC: |
DC 12 ... 24 V |
Switching current DC: |
16 A |
Min. switching current: |
100 mA |
Switch-on current 150 µs: |
600 A |
Switch-on current 600 µs: |
300 A |
Ohmic load: |
3680 W |
Capacitive load: |
16 A / 200 µF |
Lamp loads |
Incandescent lamps: |
3680 W |
HV halogen lamps: |
3680 W |
LV halogen lamps with |
inductive transformers: |
2000 VA |
electronic transformers: |
2500 W |
Fluorescent lamps T5/T8 |
non-compensated: |
3680 W |
parallel compensated: |
2500 W / 200 µF |
lead-lag circuit: |
3680 W / 200 µF |
Compact fluorescent lamps |
non-compensated: |
3680 W |
parallel compensated: |
2500 W / 200 µF |
Mercury vapour lamps |
non-compensated: |
3680 W |
parallel compensated: |
3680 W / 200 µF |
Connection, outputs |
Connection mode: |
screw terminals |
single wire: |
1 x 0.5 ... 4 mm² |
stranded without ferrule: |
1 x 0.34 ... 4 mm² |
stranded with ferrule: |
1 x 0.14 ... 2.5 mm² |
Mounting width: |
72 mm (4 rail units) |