Intended use
- Switching of lighting
- Operation with suitable eNet radio transmitters
- Operation with power supply (ref.-no. NT1220REGVDC) and receiver module (ref.-no. FMFK32REG) or eNet server
- Mounting on DIN rail according to EN 60715 in distribution boxes
Product characteristics
- Operating mode switch for: switch/push-button actuator or parameterisation via eNet server
- Status feedback to radio transmitter
- Scene operation possible
- Switchable output with Prog button
- Status indication with LED
Switching operation:
- Switch-on telegram: Device switches on
- Switch-off telegram: Device switches off
Push-button operation:
- Relay contact remains closed as long as ON or OFF telegrams are being received
- The maximum switch-on time is 60 seconds
Can be set with eNet server:
- Flash function
- Run-on time
- Switch-on delay / switch-off delay
- Operation as NO or NC contacts
- Switch-off warning
- Minimum switching repeat time
- Operating locks
- Continuous on, Continuous off
Supplementary functions with eNet server:
- Fully-encrypted radio transmission (AES-CCM) from eNet Server software version 2.0
- Update of the device software
- Reading of error memory
Technical data
Rated voltage: |
AC 230 V ~, 50/60 Hz |
Ambient temperature: |
−5 ... +45 °C |
Switching current at AC 230 V ~ |
Ohmic: |
16 A |
For switching current > 10 A connecting cable 2.5 mm² |
Fluorescent lamps: |
4 AX |
Contact type: |
µ |
Stand-by power: |
max. 0.2 W |
Connected load |
Incandescent lamps: |
2300 W |
HV halogen lamps: |
2000 W |
Electronic transformers: |
1500 W |
HV LED lamps: |
typical 500 W |
Compact fluorescent lamps: |
typical 500 W |
Inductive transformers: |
1000 VA |
Fluorescent lamps non-compensated: |
920 VA |
Capacitive load: |
690 VA (560 µF) |
Connection, outputs |
Connection mode: |
screw terminals |
single wire: |
1 x 1.5 ... 4 mm² |
stranded without ferrule: |
1 x 0.75 ... 4 mm² |
stranded with ferrule: |
1 x 0.5 ... 2.5 mm² |
Mounting width: |
36 mm (2 rail units) |
Bus line |
Rated voltage: |
DC 12 V SELV |
Current consumption: |
max. 20 mA |
Connection bus: |
terminal |
Cable length: |
max. 3 m |
|