Intended use
- Switching of lighting
- Operation with suitable eNet radio transmitters
- Operation with power supply (ref.-no. NT1220REGVDC) and receiver module (ref.-no. FMFK32REG) or eNet server
- Mounting on DIN rail according to EN 60715 in distribution boxes
Product characteristics
- Operating mode switch for: switch/push-button actuator or parameterisation via eNet server
- Status feedback to radio transmitter
- Scene operation possible
- Switchable output with Prog button
- Status indication with LED
Switching operation:
- Switch-on telegram: Device switches on
- Switch-off telegram: Device switches off
Push-button operation:
- Relay contact remains closed as long as ON or OFF telegrams are being received
- The maximum switch-on time is 60 seconds
Can be set with eNet server:
- Flash function
- Run-on time
- Switch-on delay / switch-off delay
- Operation as NO or NC contacts
- Switch-off warning
- Minimum switching repeat time
- Operating locks
- Continuous on, Continuous off
Supplementary functions with eNet server:
- Fully-encrypted radio transmission (AES-CCM) from eNet Server software version 2.0
- Update of the device software
- Reading of error memory
Technical data
| Rated voltage: |
AC 230 V ~, 50/60 Hz |
| Ambient temperature: |
−5 ... +45 °C |
| Switching current at AC 230 V ~ |
| Ohmic: |
16 A |
| For switching current > 10 A connecting cable 2.5 mm² |
| Fluorescent lamps: |
4 AX |
| Contact type: |
µ |
| Stand-by power: |
max. 0.2 W |
| Connected load |
| Incandescent lamps: |
2300 W |
| HV halogen lamps: |
2000 W |
| Electronic transformers: |
1500 W |
| HV LED lamps: |
typical 500 W |
| Compact fluorescent lamps: |
typical 500 W |
| Inductive transformers: |
1000 VA |
| Fluorescent lamps non-compensated: |
920 VA |
| Capacitive load: |
690 VA (560 µF) |
| Connection, outputs |
| Connection mode: |
screw terminals |
| single wire: |
1 x 1.5 ... 4 mm² |
| stranded without ferrule: |
1 x 0.75 ... 4 mm² |
| stranded with ferrule: |
1 x 0.5 ... 2.5 mm² |
| Mounting width: |
36 mm (2 rail units) |
| Bus line |
| Rated voltage: |
DC 12 V SELV |
| Current consumption: |
max. 20 mA |
| Connection bus: |
terminal |
| Cable length: |
max. 3 m |
|