Power-supplying and monitoring of the KNX system voltage, 160 mA Power Supply with 30 V DC auxiliary supply and manual reset key.
Function description
- 160 mA supply voltage
- 30 V DC auxiliary supply
- Power-supplying and monitoring of the KNX system voltage
- Reset key for 20 sec. bus reset
- Continuous short-circuit protection
Technical data
| Operating voltage KNX |
Bus voltage, ≤12 mA |
| Operating voltage |
230 – 240 V AC 50 – 60 Hz |
| Frequency |
50 – 60 Hz |
| Stand-by consumption |
≤0.8 W |
| Width |
4 modules |
| Installation type |
DIN rail |
| Type of connection |
KNX bus terminal |
| KNX output |
1 line with integrated throttle drive |
| Nominal voltage KNX |
30 V DC, ± 2 V, SELV |
| Nominal current KNX |
160 mA |
| Uninterrupted short-circuit current |
max.0.5 A |
| Mains failure bridging time |
min.130 ms |
| Ambient temperature |
-5°C ... 45°C |
| Protection class |
II according to EN 60 730-1 |
| Type of protection |
IP 20 |