For higher lamp loads the 4-way C load switching actuator MIX2 also comes with current recognition and can be upgraded to maximum of 12 channels with extension moduels.
Function description
- 4-way C load switching actuator MIX2
 
- With current recognition
 
- For higher lamp loads
 
- Base module MIX2
 
- Can be upgraded to maximum of 12 channels
 
- Up to two extension modules MIX or MIX2 can be connected to one base module
 
- Device and KNX bus module can be swapped independently of each other
 
- Removable KNX bus module enables devices to be changed without reprogramming
 
- Manual set-up and use of switching actuators is possible without KNX bus module
 
- LED switching status display for each channel
 
- Manual operation on device (even without bus connection)
 
- Adjustable characteristics: e.g. switching, delayed switching, pulse function
 
- Links, type of contact (NC contact/NO contact) and participation in central commands such as continuous On, continuous Off, central switching and save/call up scene
 
- Switching functions: On/Off, pulse, On/Off delay, staircase light with warning
 
- Logical links: e.g. lock, AND, release, OR
 
Technical data
| Operating voltage KNX | 
Bus voltage, ≤4 mA | 
| Operating voltage | 
110 – 240 V AC 50 – 60 Hz | 
| Frequency | 
50 – 60 Hz | 
| Stand-by consumption | 
~1.3 W | 
| Capacity loss max. | 
2.4 W | 
| Installation type | 
DIN rail | 
| Width | 
4 modules | 
| Type of connection | 
KNX bus terminal | 
| Max. cable cross section | 
Solid wire: 0.5 mm² (Ø 0.8) to 6 mm² | Stranded wire with end sleeve: 0.5 mm² to 4 mm² | 
| Number of channels | 
4 | 
| Type of contact | 
NO contact, 16 A, 10 A | 
| Opening width | 
< 3 mm | 
| Resistive load | 
3680 W | 
| Capacitive load | 
200 µF | 
| Incandescent/halogen lamp load | 
2600 W | 
| Fluorescent lamp load (conventional) parallel-corrected | 
2000 W (200 µF) | 
| Fluorescent lamp load (electronic ballast) | 
1650 W | 
| Energy saving lamps | 
410 W | 
| LED lamp < 2 W | 
75 W | 
| LED lamp 2-8 W | 
850 W | 
| LED lamp > 8 W | 
850 W | 
| Inrush current | 
max. 1500 A / 200 µs | 
| Voltage output | 
240 V AC | 
| Switching output | 
Potential-free | 
| Switching of various phases | 
Possible | 
| Suitable for SELV | 
Yes if all channels switch at SELV | 
| Accuracy current measurement | 
I > 1 A: ± 8 % of measured value; I < 1 A: ± 100 mA; lowest measurable value: 150 mA | 
| C load | 
Yes | 
| Type | 
Base module | 
| Ambient temperature | 
-5°C ... 45°C | 
| Type of protection | 
IP 20 | 
| Protection class | 
II according to EN 60 669 |